High Temperature Ground Source Heat Pump range
Below are the technical characteristics of the four water / water heat-pump models in the PACAO-65 range. You may also return to read the ground source heat-pump general description.
GSHP Technical characteristics
| PACAO-65 Models |
Unit |
PAC-AO 65 13M |
PAC-AO 65 13T |
PAC-AO 65 18T |
PAC-AO 65 24T |
| House heating output |
Watt |
13 600 |
13 500 |
18 900 |
24 500 |
| Power input |
Watt |
3 068 |
3 000 |
4 395 |
5 444 |
| C.O.P |
|
4,4 |
4,5 |
4,3 |
4,5 |
| Electrical Power Supply |
Volt |
230/1/50Hz |
400/3/+N 50Hz |
| Water Flow |
m³/h |
2.3 |
2.,3 |
3.2 |
4.2 |
| Fluid |
HFC |
R407C |
| Hydraulic Connection |
Inches |
1"(26x34) |
| Heat Exchanger |
Stainless steel |
316L |
| Bodywork + Fittings |
Stainless steel |
304L |
| Weight |
Kg |
85 |
85 |
92 |
158 |
| Height/Length/Width |
mm |
750/595/500 |
| Noise/acoustic level at 10m |
dBA |
35 |
37 |
*The values seen above, relate to tests with the following conditions:
| Evaporator |
Condensor |
- Entry temperature: +10°C
- Exit temperature: +7°C
|
- Entry temperature: +30°C
- Exit temperature: +35°C
|
Functional range - limitations :
| Evaporator |
Condensor |
- Entry temperature: 0°C
- Exit temperature: -3°C
|
- Entry temperature: +60°C
- Exit temperature: +65°C
|